>> Introduction
DAB5-63 are intended for protecting distribution and group systems having different loads:
- electric appliances, lighting – V characteristic switches;
- drives with moderate starting currents (compressor, fan group) – C characteristic switches;
- drives with high starting currents (hoisting mechanisms, pumps) – D characteristic switches;
Miniature circuit breaker DAB5-63 are recommended for use in electrical distribution panels of residential and public buildings.
>> Advantages
· Two types of short circuit protection.
· Wide range of operating temperatures from –40 to +50° С.
· Updated wider engagement lever with improved contact area.
· Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.
MCB DAB5-63 | ||||||
For protection of general power distribution (IEC/EN 60898-1) | ||||||
Poles |
1P |
2P |
3P |
4P |
||
Electrical performance | ||||||
Functions |
short circuit protection,overload protection,isolationg,control |
|||||
Rated frequency f (Hz) |
50-60Hz |
|||||
Rated working voltage Ue V AC |
230/400 |
400 |
||||
Rated current In(A) |
6,10,16,20,25,32,40,50,63 |
|||||
Rated insulated voltage Ui (V) |
500 |
|||||
Impulse withstand voltage Uimp (kV) |
4 |
|||||
Instantaneous tripping type |
DAB5-63N |
B/C/D |
||||
DAB5-63H |
B/C/D |
|||||
Rated short circuit Icn(kA) |
DAB5-63N |
4.5 |
||||
DAB5-63H |
6 |
|||||
Release type |
Thermal magnetic type |
|||||
Service life(O~C) |
Mechanical |
Actual value |
20000 |
|||
Standard value |
4000 |
|||||
Electrical |
Actual value |
8000 |
||||
Standard value |
4000 |
|||||
Connection and installation | ||||||
Protectiom degree |
IP20 |
|||||
Wire mm² |
1~35 |
|||||
Working temperature |
-5 ~+40℃ |
|||||
Resistance to humidity and heat |
Class 2 |
|||||
Altitude above sea |
≤2000 |
|||||
Relative humidity |
+20℃ , ≤90% ;+40℃ , ≤50% |
|||||
Pollution degree |
2 |
|||||
Installation environment |
Avoid obvious shock and vibration |
|||||
Installation class |
Class Ⅱ , Class Ⅲ |
|||||
Mounting |
DIN35 rail |
|||||
Combination with accessories | ||||||
Auxiliary contact |
Yes |
|||||
Alarm contact |
Yes |
|||||
Shunt release |
Yes |
|||||
Undervoltage release |
Yes |
|||||
Auxiliary contact+Alarm contact |
Yes |
|||||
Dimensions(mm) (WxHxL) |
a |
17.5 |
35 |
52.5 |
70 |
|
b |
80.2 |
80.2 |
80.2 |
80.2 |
||
c |
76.5 |
76.5 |
76.5 |
76.5 |