Input voltage range, “0″ -30..+5 V
Input voltage range, “1″ 15..30 V
Input impedance 3.5 kΩ
Isolation Groupwise isolated from ground, 2 groups with 8 channels
Filter times (digital, selectable) 2, 4, 8, 16 ms
Current limiting Sensor power can be current limited by the MTU
Maximum field cable length 600 meters (656 yards)
Rated insulation voltage 50 V
Dielectric test voltage 500 V a.c.
Power dissipation Typ. 1.8 W
Current consumption +5 V Modulebus 50 mA
Current consumption +24 V Modulebus 0
Current consumption +24 V external 0