China JCSD-60 Surge protection Device 30/60kA Surge Arrestor Manufacturer and Supplier | TCT

JCSD-60 Surge protection Device 30/60kA Surge Arrestor

Short Description:

Surge protection devices (SPDs) are essential components of any electrical system that help protect equipment from damaging voltage surges caused by lightning strikes, power outages, or other electrical disturbances. JCSD-60 SPDs are designed to divert excess electrical current away from sensitive equipment, reducing the risk of damage or failure.


Product Detail

Product Tags

Product Detail

Introduction:

JCSD-60 Surge protection devices are designed to absorb and dissipate the excess electrical energy caused by power surges, ensuring that the equipment connected to the system is not damaged. JCSD-60 SPDs can help prevent costly equipment downtime, repairs, and replacements.

JCSD-60 surge arrestors are designed to absorb and dissipate the excess electrical energy caused by power surges, ensuring that the equipment connected to the system is not damaged. This SPDs can help prevent costly equipment downtime, repairs, and replacements. The devices are also designed to be easy to install and maintain.

JCSD-60 Spds is characterized by its capacity to safely discharge current with 8/20 µs wave form. T2 and T2+3 SPDs are available in specific multi-pole versions for all distribution systems.

Our JCSD-60 surge protection device is built with the latest technology and a sleek, modern design that will blend seamlessly with any electrical system. It is DIN-rail mountable, making it easy to install and use in a variety of settings.

One of the most critical features of our surge protection device is its nominal discharge current In 30kA (8/20 µs) per path. This means that it can withstand high levels of electrical surges without causing any harm to your equipment. Furthermore, its maximum discharge current Imax 60kA (8/20 µs) makes it a powerful tool in preventing damage caused by surges.

Our JCSD-60 Surge protection device is ergonomically designed to ensure maximum protection for all of your electronics. It is crafted from high-quality materials and carefully tested to ensure that it can withstand any power surge.

Product Description:

Main Features
● Available in 1 Pole ,2P+N ,3 Pole,4 Pole, 3P+N
● MOV or MOV+GSG Technology
● Nominal discharge current In 30kA (8/20 µs) per path
● Maximum discharge current Imax 60kA (8/20 µs)
● Plug-in module design with status indication
● Visual Indication: Green=OK, Red=Replace
● Optional Remote indication contact
● Din Rail Mounted
● Pluggable replacement modules
● Suitable for TN, TNC-S, TNC and TT systems
● Complies with IEC61643-11 & EN 61643-11

Technical Data
● Type 2
● Network, 230 V single-phase, 400 V 3-phase
● Max. AC operating voltage Uc: 275V
● Temporary Over Voltage (TOV) Charasteristics – 5 sec. UT: 335 Vac withstand
● Temporary Over Voltage (TOV) Charasteristics – 120 mn UT: 440 Vac disconnection
● Nominal discharge current In: 30 kA
● Max. discharge current Imax:60kA
● Total Maximum discharge current Imax total:80kA
● Withstand on Combination waveform IEC 61643-11 Uoc:6kV
● Protection level Up:1.8kV
● Protection level N/PE at 5 kA :0.7 kV
● Residual voltage L/PE at 5 kA:0.7 kV
● Admissible short-circuit current:25kA
● Connection to Network:By screw terminals: 2.5-25 mm²
● Mounting:Symmetrical rail 35 mm (DIN 60715)
● Operating temperature:-40 / +85°C
● Protection rating:IP20
● Failsafe mode: Disconnection from AC network
● Disconnection indicator:1 mechanical indicator by pole – Red/Green
● Fuses:50 A mini. – 125 A max. – Fuses Type gG
● Standards compliance:IEC 61643-11 / EN 61643-11

Technology MOV, MOV+GSG are available
Type Type2
Network 230 V single-phase
400 V 3-phase
Max. AC operating voltage   Uc 275V
Temporary Over Voltage (TOV) Charasteristics – 5 sec.   UT 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics – 120 mn   UT 440 Vac disconnection
Nominal discharge current    In 30 kA
Max. discharge current  Imax 60kA
Withstand on Combination waveform IEC 61643-11  Uoc 6kV
Protection level  Up 1.8kV
Protection level N/PE at 5 kA 0.7 kV
Residual voltage L/PE at 5 kA 0.7 kV
Admissible short-circuit current 25kA
Connection to Network By screw terminals: 2.5-25 mm²
Mounting Symmetrical rail 35 mm (DIN 60715)
Operating temperature -40 / +85°C
Protection rating IP20
Failsafe mode  Disconnection from AC network
Disconnection indicator 1 mechanical indicator by pole – Red/Green
Fuses 50 A mini. – 125 A max. – Fuses Type gG
Standards compliance IEC 61643-11 / EN 61643-11

Type 1
SPD which can discharge partial lightning current
with a typical waveform 10/350 μs (Class I test). Usually employs spark gap technology.
Type 2
SPD which can prevent the spread of overvoltages in the electrical installations and protects equipment connected to it. It usually employs metal oxide varistor (MOV) technology and is characterised by an 8/20 μs current wave (Class II test)

Type – Surge protection devices are classified into types according to their discharge capacity. The term Class is also commonly used.

Iimp – Impulse current of 10/350 μs waveform
associated with Type 1 SPD’s

In – Surge current of 8/20 μs waveform
associated with Type 2 SPD’s

Up – The residual voltage that is measured across
the terminal of the SPD when In is applied

Uc – The maximum voltage which may be
continuously applied to the SPD without it conducting.


  • Previous:
  • Next:

  • Write your message here and send it to us