This AC surge protective device is applied low voltage standard IEC EN 61643-11 to protect against AC power line system and other equipment from over voltage and instantaneous over voltage damage. It has advantages of large discharge current, fast respond time and low residual voltage.
1. High discharge capacity, quick response, pluggable.
2. Fast response time, din rail installation.
3. Double thermal disconnection devices, provide more reliable protection.
4.Green window means normal, red means defect, need to change module.
5. Remote alarm terminal optional.
6. Voltage can be customized.
Model |
LY1-D20 |
Test standard |
IEC/EN 61643-11;GB18802.11 |
IEC test classification |
T2/Class II |
Maximum continuous operating voltage Uc |
275V/385V AC |
Nominal discharge current (8/20µs) |
10kA |
Maximum discharge current(8/20µs) |
20kA |
Voltage protection level Up |
≤1.2kV(275V AC ) ≤1.5kV(385V AC) |
Response time Ta |
25ns |
Poles |
1P 2P 3P 4P 1P+N-PE 3P+N-PE |
Fuse or circuit breaker selection(A) |
32A |
Connecting cable |
4mm2(L-N); 6mm2(PE) |
Method of Installation |
35mm Din Rail |
Type of remote signaling contact Switching contact(Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
Switching capacity |
AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A |
Cross-sectional area for remote signal contact |
Max. 1.5mm2 solid / flexible |
Operating temperature range |
40°C…+80°C |
Shell material |
UL94-V0 fireproof material |