Environmental conditions:
The main technical parameters:
NO | Item | Units | Technical parameters | |||||
1 | Rated voltage | kV | 12 | |||||
2 | Maximum working voltage | kV | 12 | |||||
3 | Rated current | A | 630/1250 | 630/1250 | 630/1250 | |||
4 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | |||
5 | Rated short circuit closing current | kA | 50 | 63 | 80 | |||
6 | Rated peak withstand current | kA | 50 | 63 | 80 | |||
7 | 4S rated short circuit withstand current | kA | 20 | 25 | 31.5 | |||
8
|
Rated insulation level | Power frequency withstand voltage (before and after rated breaking) | kV | 42(Fracture:48) | ||||
Impact withstand voltage (before and after rated breaking) | 75(Fracture:84) | |||||||
9 | Rated operation sequence | 0-0.3s-Co-180s-Co | ||||||
10 | Mechanical life | times | 10000 | |||||
11 | Rated short circuit current breaking times | times | 50 | |||||
12 | Operating mechanism rated closing voltage (DC) | V | 110,220 | |||||
13 | Operating mechanism rated trip current (DC) | V | 110,200 | |||||
14 | Contact stroke | mm | 11±1 | |||||
15 | Overtravel (contact spring compression length) | mm | 3.5±0.5 | |||||
16 | Three-phase split and close bounce time | ms | ≤2 | |||||
17 | Contact closing bounce time | ms | ≤2 | |||||
18 | Average opening speed | m/s | 1.2±0.2 | |||||
19 | Average closing speed | m/s | 0.6±0.2 | |||||
20 | Opening time | At the highest operating voltage | s | ≤0.05 | ||||
At the lowest operating voltage | ≤0.08 | |||||||
21 | Closing time | S | 0.1 | |||||
22 | Main loop resistance of each phase | μΩ | 60 | 50 | ||||
23 | Dynamic and static contacts allow wear cumulative thickness | mm | 3 |