China YBM(P)-12/0.4 Intelligent preassembled integrated substation Manufacturer and Supplier | TCT

YBM(P)-12/0.4 Intelligent preassembled integrated substation

Short Description:

Widely used in urban public power distribution, high-rise buildings, living quarters, industrial and mining enterprises, national defense construction, oil fields and temporary construction projects in the distribution system to accept and distribute electric energy.

We are the Factory that guarantees supply chain and product quality

Acceptance: Distribution, Wholesale,Custom,OEM/ODM

We are China’s famous sheet metal factory, is your trusted partner

We have a big brand of cooperative production experience(You’re next)

Any inquiries→ We are happy to reply, please send your questions and orders

No MOQ limit,any installation can be communicated at any time


Product Detail

Product Tags

YBM(P)-12/0.4 Intelligent preassembled substation is a power distribution device that combines high-voltage electrical equipment, transfoer, low-voltage electrical equipment, etc. into a compact complete set of equipment, which is suitable for AC 50HZ, 10kV power system. It is widely used in urban public power distribution, high-rise buildings, living quarters, industrial and mining enterprises, national defense construction, oil fields and temporary construction of engineering and other places for accepting and distributing electric energy in the power distribution system. The product has the advantages of compact structure, small size, small footprint, quick installation and easy maintenance.

Product characteristics

  • 1. The framework of substation is made of surface treated section steel, which has sufficient mechanical strength and rigidity.
  • 2. The shell material can be stainless steel plate, cold-rolled steel plate, composite steel plate, metal inlaid antique wood strip, cement, etc.;
  • 3. Each room is separated into an independent small room by steel plate, which can be arranged as a “mesh” font, “product” font and other fos;
  • 4. In order to facilitate monitoring and maintenance, transfoer room, high and low pressure room are equipped with lighting devices;
  • 5. The top cover is double-layer structure, which can prevent heat radiation from increasing the indoor temperature;
  • 6, the transfoer is based on natural ventilation, when the temperature of the transfoer room exceeds the set temperature, the axial fan installed on the top automatically starts to control the temperature of the transfoer room;
  • 7. Perfect protection perfoance, easy operation, high pressure side has a complete five anti-function to ensure the safety of maintenance;
  • 8. Compact structure, beautiful appearance, can be coordinated with the surrounding environment;

Conditions of use

  • 1.Altitude ≤1000m
  • 2. Ambient temperature: -25C-40° C, maximum temperature difference <
  • 3. Relative humidity: The average daily relative humidity does not exceed 95%;
  • 4. The average monthly relative humidity does not exceed 90%;
  • 5. Earthquake resistance: ground horizontal acceleration < 0.4 m/s2;
  • 6. Ground vertical acceleration 0.2m/s2;
  • 7. Pollution level: Ⅲ;
  • 8. There is no severe vibration and shock, and there is fire, chemical corrosion, explosion danger. Start to control the temperature of the transfoer room;
  • 9. Perfect protection perfoance, easy operation, high pressure side has a complete five anti-function to ensure the safety of maintenance;
  • 10. Compact structure, beautiful appearance, can be coordinated with the surrounding environment;

Technical Parameter

sort

Project name

unit

Main technical parameters

High Voltage unit

Rated frequency

Hz

50

Rated voltage

kV

7.2

Rated current of main bus

A

630, 1250, 1600

Rated short-time withstand current/time

K A/s

20/4,  25/3, 31.5/4

Rated peak withstand current

kA

50, 63, 80

Imin power frequency withstand voltage (to ground/new port)

kV

32/36 42/48 115/95

Lightning impulse withstand voltage

kV

60/70 75/85 185/215

Rated short-circuit breaking current

kA

20, 25, 31.5

Short-time ground loop withstand current/time

kA/s

20/2, 20/4

Rated short-circuit closing current of the main circuit

kA

50, 63, 80

Rated active load breaking current

A

630

Rated closed-loop breaking current

A

630

Rated cable charging breaking current

A

10

Rated capacity of no-load transfoer for breaking

kVA

1250

Rated transfer current

A

1700

Mechanical life

Time

3000, 5000, 10000

Low pressure unit

Rated frequency

Hz

50

Rated voltage

kV

0.4/0.23

Rated insulation voltage

V

690

Rated current of main loop

A

100~3200

Rated short-time withstand current

kA/s

30/1, 50/1, 100/1

Rated peak withstand current

kA

63, 105, 176

5s power frequency withstand voltage

kV

2.5

Transfoer unit

type

Oil-immersed, dry type

Rated frequency

Hz

50

Rated voltage

kV

12(7.2)/0.4(0.23)

Rated capacity

kVA

30~1600

1min power frequency withstand voltage

kV

35(25)
28(20)

Lightning impulse withstand voltage

kV

75(60)

Impedance voltage

%

46

Tapping range

±X2.5%±X5%

Coupling group

Y, yn0D, yn11

BOX

High and low pressure chamber protection class

IP33D

Protection class of transfoer room

IP23D

Sound level (oil immersed/dry)

dB

≤50/55

Secondary circuit withstand voltage level

kV

1.5/2

Meet The Standard

This product confos to the standards: GB1094.1, GB3906, GB7251, GB/T17467, DL/T537 and other related standards


  • Previous:
  • Next:

  • Write your message here and send it to us